Exide-technologies Section 95.10 User Manual

Browse online or download User Manual for Power suppliers Exide-technologies Section 95.10. Exide Technologies Section 95.10 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 18
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
INSTALLATION
&
OPERATING
INSTRUCTIONS
A Division of Exide Technologies
®
SECTION 95.10 2012-07 SECTION 95.10 2012-07
GNB Industrial Power
USA Tel: 888.898.4462
Canada Tel: 800.268.2698
www.gnb.com
GNB Industrial Power, a division of Exide technologies, is a
global leader in network power applications including
communication/data networks, UPS systems for computers
and control systems, electrical power generation and
distribution systems, as well as a wide range of other
industrial standby power applications. With a strong
manufacturing base in both North America and Europe and a
truly global reach (operations in more than 80 countries) in
sales and service, GNB Industrial Power is best positioned to
satisfy your back up power needs locally as well as all over
the world.
Based on over 100 years of technological innovation the
Network Power group leads the industry with the most
recognized global brands such as ABSOLYTE
®
, GNB
®
FLOODED CLASSIC
®
, MARATHON
®
, ONYX
®
, RELAY GEL
®
,
SONNENSCHEIN
®
, and SPRINTER
®
. They have come to
symbolize quality, reliability, performance and excellence in
all the markets served.
GNB Industrial Power takes pride in its commitment to a
better environment. Its Total Battery Management program,
an integrated approach to manufacturing, distributing and
recycling of lead acid batteries, has been developed to
ensure a safe and responsible life cycle for all of its products.
GNB Industrial Power
The Industry Leader.
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - INSTRUCTIONS

INSTALLATION&OPERATINGINSTRUCTIONSA Division of Exide Technologies®SECTION 95.10 2012-07 SECTION 95.10 2012-07GNB Industrial PowerUSA – Tel: 888.8

Page 2

7.6 CONNECTION RESISTANCEElectrical integrity of connections can be objectively established by measuring theresistance of each connection. These resis

Page 3

NOTE: Time periods listed in Table A are for temperatures from 21°C (70°F) to 32°C(90°F); for temperatures 13°C (55°F) to 20.5°C (69°F), double the nu

Page 4

Minimum float voltage (temperature corrected) is 2.21 VPC. Temperature correctiondoes not apply below this value.Maximum float voltage (temperature co

Page 5

9.4 DETERMINING STATE OF CHARGEIf the normal connected load is constant (no emergency load connected), the followingmethod can be used to determine th

Page 6

9.6 EFFECTS OF FLOAT VOLTAGEFloat voltage also has a direct effect on the service life of your battery. A float voltageabove the recommended limits re

Page 7 - Figure 1

SECTION 11 - MAINTENANCE SCHEDULEA pilot unit is selected in the series string to reflect the general condition of all units inthe battery. The pilot

Page 8

SECTION 12 - TAP CONNECTIONSTap connections should not be used on a battery. This can reduce battery life.SECTION 13 - TEMPORARY NON-USEAn installed b

Page 9

14ADivision of Exide TechnologiesRELAY GEL BATTERY MAINTENANCE REPORTBatt.Batt.WHEN ADVICE IS DESIRED, PLEASE FORWARD A DUPLICATE OF THIS REPORT TO YO

Page 10

INSTALLATION&OPERATINGINSTRUCTIONSA Division of Exide Technologies®SECTION 95.10 2012-07 SECTION 95.10 2012-07GNB Industrial PowerUSA – Tel: 888.8

Page 11

INDEXPageSection 1 - GENERAL INFORMATION1.0 Relay Gel Batteries 1Section 2 - SAFETY PRECAUTIONS2.0 Safety Alert 12.1 Sulfuric Acid Burns 12.2 Explosiv

Page 12

INDEX (continued)PageSection 7 - ELECTRICAL INSTALLATION CONSIDERATIONS7.0 Connecting Cables 57.1 Paralleling 57.2 Connection Preparation 57.3 Torquei

Page 13

SECTION 1 - GENERAL INFORMATION1.0 RELAY GEL VRLA BATTERIESIn normal use, the battery will not release hydrogen gas or acid mist, and will not leakaci

Page 14

Never lay tools or other metallic objects on the batteries as shorting, explosions andpersonal injury may result.Multi-cell systems attain high voltag

Page 15

3.1 CONCEALED DAMAGEWithin 15 days of receipt, examine all batteries for concealed damage. If damage is noted,immediately request an inspection by the

Page 16

5.1 BATTERY ORIENTATIONThe RELAY GEL battery can only be installed in a vertical orientation with the postspointing up (per Figure 1). This battery ma

Page 17 - REPRESENTATIVE

5.6 OPEN CIRCUIT VOLTAGE CHECKThe voltage of each unit should be checked to insure the voltage is at least 12.6 volts. Ifany unit has a voltage lower

Page 18

7.3 CONNECTION TORQUEINGAfter cleaning contact surfaces, install all connectors hand tight to allow for final alignmentof units. Once final alignment